System simulation for an untreated sewage source heat pump (USSHP) in winter
Author(s): Na Qin; Peng Z. Hao
Format Member Price Non-Member Price
PDF $17.00 $21.00

Paper Abstract

The paper discusses the system characteristics of an untreated sewage source heat pump in winter. In this system, the sewage enters into the evaporator directly. The variable parameters to control the system contain the sewage temperature at evaporator inlet and the water temperature at condenser inlet. It is found that most parameters, except the condensation heat transfer coefficient, change in the form of sine wave the same as the sewage temperature at inlet. The heating load and consumed power are 12.9kW and 3.45kW when the sewage temperature at inlet is 13°C. COP is about 3.75 in the range of the sewage temperature at inlet of 12-13°C.

Paper Details

Date Published: 23 January 2017
PDF: 7 pages
Proc. SPIE 10322, Seventh International Conference on Electronics and Information Engineering, 103220O (23 January 2017); doi: 10.1117/12.2265269
Show Author Affiliations
Na Qin, Tianjin Univ. of Technology (China)
Peng Z. Hao, Tianjin Institute of Urban Construction (China)