The Evaluation Of Infrared Imaging Systems Used For Building Inspections
Author(s): Richard A Grot; Yui-May Chang
Format Member Price Non-Member Price
PDF $14.40 $18.00
cover GOOD NEWS! Your organization subscribes to the SPIE Digital Library. You may be able to download this paper for free. Check Access

Paper Abstract

The results of the laboratory evaluation of three high resolution infrared imaging systems are presented. The systems were evaluated for their minimum resolvable temperature difference (MRTD) at spatial frequencies from 0.02 to 0.16 cycles per milliradian and at ambient temperatures in the range of -7° C to 20° C. The results of these tests are compared with the predicted dependence of the MRTD given in the ASHRAE Standard 101-83. It is shown that the dependence on temperature of the MRTD of two of the systems is predicted well by the theory given in the ASHRAE standard. The calibration curves of the infrared imaging systems are given. These are in good agreement with those given by the manufacturers of the equipment.

Paper Details

Date Published: 27 March 1984
PDF: 6 pages
Proc. SPIE 0446, Thermosense VI: Thermal Infrared Sensing for Diagnostics and Control, (27 March 1984); doi: 10.1117/12.939170
Show Author Affiliations
Richard A Grot, National Bureau of Standards (United States)
Yui-May Chang, National Bureau of Standards (United States)

Published in SPIE Proceedings Vol. 0446:
Thermosense VI: Thermal Infrared Sensing for Diagnostics and Control